Size |
483 x 133 x 294 mm (19.0 x 5.25 x 11.5 ins) |
Weight |
9.5 kg (21 lbs) |
Enclosure material |
Aluminum alloy |
Mounting |
Rack mounted (3u format). Wall mounted and floor standing cabinets are optional, dimensions on request. |
Channels |
16 per rack |
Operating temperature |
0°C to +50°C (32°F to +122°F) |
Humidity |
0-95% non-condensing |
Inputs |
Gas 2 or 3 wire 4-20mA (sink or source), or mV bridge |
|
Fire – smoke & heat detectors, manual call-points Maximum of 32 loopes per rack (ie 16 twin zone fire modules) |
Outputs |
Analogue 16 x 4-20mA, max. load 960 Ohms or 1-5 V, min. load 100 Ohms |
|
External audible/visual alarm drive Powered 24 V dc, max load up to 200mA for each alarm level. |
Relays |
Type Up to 84 DPCO contacts rated 5 A @ 250 V ac, non-inductive load |
|
Assignment – Common Alarm 1, Alarm 2, Alarm 3, Fault
– Per channel Gas alarms 1, 2 & 3, fire &
fault
– Voting Up to 16, configurable
– Relay modes Energised/de-energised,
latched/non-latched, time-delayed, pulsed |
Digital communications |
With PanelsPro or SetGMon only |
Event logging |
Built-in datalogger – data available via communication links with PanelsPro or SetGMon only |
Panel indication |
Channel number: 4 lines x 20 characters
Gas reading: On main LCD plus green LED bar-graph on channel card
Measurement units: % LEL, ppm, % Vol, Fire
System fault – integrity watchdog: Yellow LED |
Alarm indication |
As standard: 3 individual & 3 common alarms (red LED); Fault – individual & common fault (yellow LED); Inhibit – individual inhibit (yellow LED) |
Power |
AC mains: 100 – 260 V ac 50/60 Hz external
DC: 27.6 V
Battery back-up: external |
Approvals |
Low voltage directive – EN61010-1
EMC Directive – EN 50082-1
EMC Directive – EN 50081-1EN 50270, EN61000-6-4ATEX: Conforms to EN60079-25 in configuration with Zener Barrier Baseefa 05Y0090/1 |