Gas Hazards in Battery Power Storage

Batteries are effective at reducing power outages since they can also store excess traditional grid energy. The energy stored within batteries can be released whenever a large volume of power is needed, such as during a power failure at a data centre to prevent data being lost, or as a back-up power supply to a hospital or military application to ensure the continuity of vital services. Large scale batteries can also be used to plug short-term gaps in demand from the grid. These battery compositions can also be used in smaller sizes to power electric cars and may be further scaled down to power commercial products, such as phones, tablets, laptops, speakers and – of course – personal gas detectors.

Gas hazards

The main gas risk emitted by batteries, specifically lead acid batteries, is hydrogen. It is possible to get both hydrogen and oxygen evolved during charging however, a lead acid battery is likely to have catalytic recombination parts internally, so oxygen is less of a risk. Hydrogen is always a cause for concern, as it can collect and build up. A situation that is obviously worsened when they are charged in a space with a poor airflow.

When charging, lead-acid batteries consist of lead and oxide at the positive terminal, and of spongy lead at the negative anode, using concentrated sulfuric acid as the electrolyte. The presence of sulfuric acid is another cause for concern if the battery leaks or is ever damaged because concentrated acids harm people, metals and the environment.

When charging batteries also emit oxygen and hydrogen because of the electrolysis process. The levels of hydrogen produced soar when a lead acid battery cell “blows” or is unable to be charged properly. The amount of gas present is relevant because high levels of hydrogen make it highly explosive, even though it is not toxic. Hydrogen has a 100% lower explosive limit of 4.0% by volume, at which level an ignition source would cause fires or for hydrogen more usually, explosions. Fires and explosions are an issue not only for the workers within the space, but also for the surrounding equipment and infrastructure.

Importance of Gas Detection Technology

Gas detection is an invaluable safety technology often equipped in battery charging rooms. Ventilation is also advised, and while helpful, it is not fool proof as fan motors can fail and should not be relied upon as the sole safety measure for battery charging areas. Fans mask the problem while gas detection notifies personnel to act before problems escalate. Gas detection systems are crucial in informing personnel of increasing gas leaks before becoming dangerous. Gas detection units comply with local building codes and NFPA 111, the National Fire Protection Association standard on stored electrical energy emergency and standby power systems. They include maintenance, operation, installation, and testing provisions regarding the system’s performance. In addition to permanent gas detection systems, handheld units are available. The benchmark products are provided by Crowcon and are listed below.

Portable Gas Detectors

Crowcon’s portable gas detectors (Gasman, Gas-Pro, T4x, Tetra 3 and T4) protect against a wide range of industrial gas hazards, with both single gas and multi-gas monitors available. With a wide range of sizes and complexities, you can find the right portable gas detection solution to meet the number and type of gas sensors you need and your display and certification requirements.

Fixed Gas Detectors

Crowcon gas detection fixed systems offer a flexible range of solutions that can measure flammable, toxic, and oxygen gases, report their presence, and activate alarms or associated equipment. Crowcon fixed gas monitoring systems (Xgard, Xgard Bright and XgardIQ) are designed to be interfaced with manual call points, fire and gas detectors, and distributed control systems (DCS).

Control Panels

Crowcon gas detection control panels offer a flexible range of solutions that can measure flammable, toxic, and oxygen gases, report their presence, and activate alarms or associated equipment. Crowcon fixed gas (Vortex, GM Addressable Controllers, Gasmaster) monitoring systems are designed to be interfaced with manual call points, fire and gas detectors and distributed control systems (DCS). In addition, each system can be engineered to drive remote annunciators and mimic panels. Crowcon has a gas detection product to suit your application regardless of your operation.

Temperature Measurement

Crowcon has extensive experience with temperature measurement. There are several models of temperature measurement, from pocket thermometers to industrial kits ranging from -99.9 to 299.9°C with probes and clamps. They are enhancing their fixed detection capabilities by adding high-temperature electrochemical sulphur dioxide detection for battery manufacturing and charging stations. This is critical during the first charge of a battery, as a fault is most likely at that time. Their fast-acting systems detect the precursors to thermal runaway and quickly terminate power to the batteries to avoid damage.

To find out more on the dangers of gas hazards in battery power visit our industry page for more information.

Car Parks are More Dangerous Than You Think

Road vehicles can emit a number of harmful gases through exhaust fumes, the most common being carbon monoxide (CO) and nitrogen dioxide (NO2). Whilst these cause gases are an issue in open air environments, there is particular cause for concern in more confined spaces such as underground and multi-storey car parks. 

Why are car parks of specific concern? 

The gases emitted through exhaust fumes are absolutely an issue regardless of where they are being emitted, and contribute to a wide variety of issues including air pollution. However, in car parks any dangers these gases cause are exasperated due to the high number of vehicles in a small, confined area and the lack of natural ventilation to ensure that these gases do not reach dangerous levels. 

What gases are present in car parks? 

Vehicles emit a variety of exhaust gases including carbon dioxide, carbon monoxide, nitrogen dioxide and sulphur dioxide. Carbon monoxide and nitrogen dioxide are the most common and are also of particular concern due to the potential negative impacts on human health that exposure to these gases can have. 

What are the dangers of gases in car parks? 

Out of the two most common gases in car parks, carbon monoxide poses the more significant threat to human health. It is an odourless, colourless and tasteless gas making it almost impossible to detect without some sort of detection equipment. 

Carbon monoxide is dangerous as it negatively impacts the transport of oxygen around the body which can cause a wide range of health problems. Breathing low levels of CO can cause nausea, dizziness, headaches, confusion and disorientation. Regularly breathing low levels of CO may cause more permanent health issues. At very high levels carbon monoxide can cause loss of consciousness and even death, with around 60 deaths attributed to carbon monoxide poisoning in England and Wales every year. 

Breathing in nitrogen dioxide also has negative health impacts including breathing and respiratory issues as well as damage to lung tissue. Exposure to high concentrations can cause inflammation of the airways and prolonged exposure can lead to irreversible damage to the respiratory system 

What regulations are there? 

In 2015, a new European Standard (EN 50545-1) was introduced, specifically relating to the detection of toxic gases such as CO and NO2 in car parks and tunnels. EN 50545-1 specifies requirements for remote gas detectors and control panels to be used in car parks. The goal of the standard is to increase the safety of gas detection systems in car parks and prevent the use of inadequate systems. Th standard also the alarm levels to be used for gas detection in car parks, shown in the table below. 

  Alarm 1  Alarm 2  Alarm 3 
CO  30 ppm  60 ppm  150 ppm 
NO2  3 ppm  6 ppm  15 ppm 

 

Crowcon Park System 

Crowcon have recently launched a new range of fixed detectors and control panels designed specifically for gas detection in car parks. 

The SMART P set of detectors, consisting of the SMART P-1 and SMART P-2 can detect CO, NO2 and petrol vapours, with the SMART P-2 offering simultaneous detection of both CO and NO2 in a single detector. The MULTISCAN++PK control panel can manage and monitor up to 256 detectors. Every product in the range has been designed to fulfil the requirements of the European Standard EN 50545-1. 

The importance of Gas Detection in the Water and Wastewater Industry 

Water is vital to our daily lives, both for personal and domestic use and industrial/commercial applications. Whether a facility focuses on the production of clean, potable water or treating effluent, Crowcon is proud to serve a wide variety of water industry clients, providing gas detection equipment that keeps workers safe around the world. 

Gas Hazards 

Apart from common gas hazards known in the industry; methane, hydrogen sulphide, and oxygen, there are bi-product gas hazards and cleaning material gas hazards that occur from purifying chemicals such as ammonia, chlorine, chlorine dioxide or ozone that are used in the decontamination of the waste and effluent water, or to remove microbes from clean water. There is great potential for many toxic or explosive gases to exist as a result of the chemicals used in the water industry. And added to these are chemicals that may be spilled or dumped into the waste system from industry, farming or building work. 

Safety Considerations  

Confined Space Entry 

The pipelines used to transport water require regular cleaning and safety checks; during these operations, portable multi-gas monitors are used to protect the workforce. Pre-entry checks must be completed prior to entering any confined space and commonly O2, CO, H2S and CH4 are monitored. Confined spaces are small, so portable monitors must be compact and unobtrusive for the user, yet able to withstand the wet and dirty environments in which they must perform. Clear and prompt indication of any increase in gas monitored (or any decrease for oxygen) is of paramount importance – loud and bright alarms are effective in raising the alarm to the user. 

Risk assessment 

Risk assessment is critical, as you need to be aware of the environment that you are entering and thus working in. Therefore, understanding the applications and identifying the risks regarding all safety aspects. Focusing on gas monitoring, as part of the risk assessment, you need to be clear on what gases may be present.  

Fit for purpose 

There is a variety of applications within the water treatment process, giving the need to monitor multiple gases, including carbon dioxide, hydrogen sulphide, chlorine, methane, oxygen, ozone and chlorine dioxide. Gas detectors are available for single or multiple gas monitoring, making them practical for different applications as well as making sure that, if conditions change (such as sludge is stirred up, causing a sudden increase in hydrogen sulphide and flammable gas levels), the worker is still protected.  

Legislation   

European Commission Directive 2017/164 issued in January 2017, established a new list of indicative occupational exposure limit values (IOELVs). IOELV are health-based, non-binding values, derived from the most recent scientific data available and considering the availability of reliable measurement techniques. The list includes carbon monoxide, nitrogen monoxide, nitrogen dioxide, sulphur dioxide, hydrogen cyanide, manganese, diacetyl and many other chemicals. The list is based on Council Directive 98/24/EC that considers the protection of the health and safety of workers from the risks related to chemical agents in the workplace. For any chemical agent for which an IOELV has been set at Union level, Member States are required to establish a national occupational exposure limit value. They also are required to take into account the Union limit value, determining the nature of the national limit value in accordance with national legislation and practice. Member States will be able to benefit from a transitional period ending at the latest on 21 August 2023.  

The Health and Safety Executive (HSE) state that each year several workers will suffer from at least one episode of work-related illness. Although, most illnesses are relatively mild cases of gastroenteritis, there is also a risk for potentially fatal diseases, such as leptospirosis (Weil’s disease) and hepatitis. Even though these are reported to the HSE, there could be significant under-reporting as there is often failure to recognise the link between illness and work.  

Under domestic law of the Health and Safety at Work etc Act 1974, employers are responsible for ensuring the safety of their employees and others. This responsibility is reinforced by regulations. 

The Confined Spaces Regulations 1997 applies where the assessment identifies risks of serious injury from work in confined spaces. These regulations contain the following key duties: 

  • Avoid entry to confined spaces, e.g., by doing the work from the outside. 
  • If entry to a confined space is unavoidable, follow a safe system of work.
  • Put in place adequate emergency arrangements before the work start. 

The Management of Health and Safety at Work Regulations 1999 requires employers and self-employed people to carry out a suitable and sufficient assessment of the risks for all work activities for the purpose of deciding what measures are necessary for safety. For work in confined spaces this means identifying the hazards present, assessing the risks and determining what precautions to take. 

Our solutions

Elimination of these gas hazards is virtually impossible, so permanent workers and contractors must depend on reliable gas detection equipment to protect them. Gas detection can be provided in both fixed and portable forms. Our portable gas detectors protect against a wide range of gas hazards, these include T4x, Clip SGD, Gasman, Tetra 3,Gas-Pro, T4 and Detective+. Our fixed gas detectors are used in many applications where reliability, dependability and lack of false alarms are instrumental to efficient and effective gas detection, these include Xgard, Xgard Bright and IRmax. Combined with a variety of our fixed detectors, our gas detection control panels offer a flexible range of solutions that measure flammable, toxic and oxygen gases, report their presence and activate alarms or associated equipment, for the wastewater industry our panels include  Gasmaster.    

To find out more on the gas hazards in wastewater and water treatment visit our industry page for more information.