Gasmaster

Compare
Category:

Overview

Gasmaster is a compact, versatile and powerful gas detection control panel that combines simple operation with an extensive array of input and output functions.

Gasmaster provides all the information you need about your gas and fire detectors at a glance. The large multi-lingual display shows gas levels from all detectors simultaneously and enables system adjustment and testing using buttons on the front panel. The Gasmaster gas detector control panel can operate ‘stand-alone’ or interface with any alarm devices and control systems using a selection of outputs.

Large display

  • All gas levels are displayed simultaneously – enables full systems status check at a glance
  • Alarm messages can be customised to indicate the name or location of any detector in alarm
  • The LCD can be set to display in many languages

User-friendly

  • Menu system is intuitive and easy to use – enables configuration changes to be made easily
  • All functions, from day-to-day operation to re-calibration, can be carried out from the front panel – routine testing can be performed rapidly
  • Event log feature – enables system fault and alarm history to be viewed

Versatile input and output features

  • Provides analogue, relay and Modbus outputs – facilitating communication around the site
  • Flexibility – Gasmaster can monitor up to four detectors in virtually any combination of gas detectors, fire zones or Environmental Sampling Unit. Software enables re-configuration and event log upload in an instant
  • Two levels of independent alarm per channel – can be configured to suit site requirements
  • Remote inhibit and re-set facilities – enables control from any point on your site
  • Compatible with a 4-20mA or mV pellistor-type gas detector – mV pellistor detectors reduce system purchase and maintenance costs

Modular design

  • You only need to purchase the required number of input modules – 1,2 and 3-channel systems can be extended later by adding additional modules

 

Specifications

Gasmaster 3
Size 288 x 278 x 110mm (11.3 x 10.9 x 4.3 inches)
Weight 4.5kg (10lbs)
Enclosure material Back-box: cast aluminium
Front cover: ABS (flame retardant)
Ingress protection IP65
Power 100-240Vac 50-60Hz or
20-30Vdc, 60W max
Battery back-up 1.2Ah batteries fitted internally
Operating temperature -10°C to +50°C (14°F to +122°F)
Inputs Gas    One 2 or 3 wire 4-20mA gas detector (sink or source) or mV pellistor flammable gas detector One to four 2 or 3 wire 4-20mA gas detectors (sink or source) or mV pellistor flammable gas detectors
Fire     One loop of up to 20 conventional smoke/heat detectors or manual call points, or one flame detector (4-20mA or digital contact signal) One to four loops of up to 20 conventional smoke/heat detectors or manual call points, or one to four flame detectors
ESU    For use with one Crowcon ESU fan
Remote inhibit/retest    Via normally open contact
Outputs Relays DPCO contacts rated 250Vac 8A
Low alarm. High alarm. Fault. Alarm relays can be set for rising or falling alarms. Hysteresis can be adjusted on low alarms
Low alarm and high alarm per channel plus common low, high and fault. Alarm relays can be set for rising or falling alarms. Hysteresis can be adjusted on low alarms
A/V alarm drive    12Vdc or 24Vdc 650mA max. drive. Suitable for +ve or -ve switched alarms
Analogue     4-20mA (current source, max. loop resistance 700?) or 1-5Vdc (min. load 50k? ) 4-20mA for each channel (current source, max. loop resistance 700?) or 1-5Vdc (min. load 50k?)
Serial link    RS-485 Modbus RTU for monitoring and control via DCS/SCADA/PLC systems
Communications port Optional port for PC configuration and event log upload
Event logging* Time-stamped log of up to 300 alarms, fault or system intervention activities
Panel indication LCD back-lit display shows gas level (in ppb, ppm, % volume or % LEL units), and scrolling alpha-numeric status indication.
LED’s for Alarm, Fault, Power and Warning. Integral 85dB sounder (at 10cm)
Approvals EMC: EN50270, EN60945, FCC: CFR 47 Part 15; ICES – 003
ATEX: May be used in a non-hazardous area as part of Intrinsically Safe System conforming to EN60079-25 Baseefa 05Y0090/1
Functional safety Validated to IEC61508
SIL2

*Event log access requires a Gasmaster PC communications kit and communications port (see Accessories). 

Accessories

Below is a small selection of the accessories available for the Gasmaster.

Communications port

Communications port

E07635

For fitment for the Gasmaster systems ordered without this already fitted.

Gasmaster PC Communications Kit

C01929

Includes software, RS-485/232 convertor and leads. Required for event-log upload.

Auxiliary Power Unit

Auxiliary Power Unit

C01954

Provides an auxiliary 24V DC supply and extended back-up. Includes 2 x 12V 7Ah batteries.

Steel brackets

Steel brackets

M01861/2

Pair of steel brackets for panel-mounting Gasmaster.

Engineers comms lead

Engineers comms lead

E07637

Connects to display PCB. RS-485-232 converter and Gasmaster PC software not included.

Downloads

Certificate

Datasheet

Manual