Flamgard Plus

Compare

Overview

Flamgard Plus is a Flameproof (Exd) flammable gas detector which uses poison-resistant pellistors to detect explosive levels of hydrocarbons, hydrogen and other flammable gases and vapours, including aviation fuel and leaded petrol vapours.

Non-intrusive calibration

  • Calibration can be performed locally without the need for hot work permits – minimises operational down-time
  • Local display and buttons enable calibration without opening the junction box

Flexible output options

  • 4-20mA current sink or source – works with a wide selection of control panels
  • 3 wire format
  • Optional relays for alarm and fault – can be used for switching local alarms

Rugged and reliable

  • Constructed using marine-grade aluminium with a stainless steel sensor housing – proven track record for operation in the harshest environments
  • Ingress protection to IP65 as standard

Low cost of ownership

  • Non-intrusive one man calibration – easy to operate and maintain
  • Long life sensors – keeps interruption to on-site activity to a minimum
  • Simple parts replacement

Wide range of sensors

  • Choice of catalytic beads for a wide selection of flammable gases and vapours – this flammable, hydrocarbon and hydrogen gas detector can be tailored to your requirements

Specifications

Size 200 x 115 x 115mm (7.9 x 6.1 x 6.1ins)
Weight 2.2kg (4.9lbs)
Ingress protection IP65
Enclosure material Junction box: Marine grade alloy
Sensor housing: 316 stainless steel
Power 10-30Vdc, 210mA max (relay version)
160mA max (non relay)
Cable entries 2 x M20 or 1/2” NPT
Operating temperature -10°C to +55°C (-14°F to 131°F) *
Humidity 0 to 99% RH non-condensing
Relays (optional) SPNO or SPNC contacts rated
30Vdc 1A (non-inductive load) for Alarm 1, Alarm 2, Fault
Display 3-digit LCD back-lit display, LED status indicator
Calibration method Via magnetically operated buttons
Electrical output 3 wire 4-20mA, sink or source
Terminals Suitable for up to 1.5mm2 cable
Sensor type Catalytic bead
Repeatability +/- 2% FSD typically
Zero drift +/- 2% FSD, 6 months typically
Response time T90 <15 seconds typically
Performance Tested in accordance with EN60079-29-1
Hazardous area zones Zone 1 or 2
Approvals Ex II 2 G
Ex db IIC T6 Tamb -20°C to +55°C
EMC compliance EN 50270, FCC: CFR 47 Part 15, ICES-003

* Figures shown exclude the sensors – Please contact Crowcon for a full list of sensor operating temperatures

Gases and Ranges

Gas LEL (% vol.) Range Available
Acetylene (C2H2)*  2.3 0-100% LEL
Ammonia (NH3) 15 0-100% LEL
Butane (C4H10 1.4 0-100% LEL
Ethanol (C2H5OH) 3.1 0-100% LEL
Ethane (C2H6) 2.4 0-100% LEL
Ethylene (C2H4) 2.3 0-100% LEL
Hexane (C6H14) 1.0 0-100% LEL
Hydrogen (H2) 4 0-100% LEL
LPG 2 0-100% LEL
Methane (CH4) 4.4 0-100% LEL
Methanol (CH3OH)  6 0-100% LEL
Pentane (C5H12) 1.1 0-100% LEL
 Petrol vapor   1.3 0-100% LEL
Propane (C3H8) 1.7 0-100% LEL
Propanol (C3H8O) 2.1 0-100% LEL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEL figures derived from EN60079-20-1:2010
*Acetylene option not available on UL certified version 

For a full list of gases download the datasheet or Crowcon.

Accessories

Below is a small selection of the accessories available for the Flamgard Plus.

Spray deflector

C01052

For use outdoor installations and to protect from water sprays, for example in water treatment or food processing plants. For extremely wet environments eg: offshore installations, use weatherproof cap, CO1442, instead.

Weatherproof cap

C01442

For offshore or other extremely wet environments in place of spray deflector.

Collector cone

C01051

For aiding detection of light gases such as methane. 38cm/15″ Dia. Includes accessory adaptor.

Stainless steel flow adaptor

C01688

For use where a gas sample is being piped to the detector. For 96HD type sensors.

Self adhesive carbon cloth filter

C01254

Removes long chain hydrocarbons where these can be a problem.

Exd Cable Gland Adaptors

 

ATEX certified Exd cable gland adaptors.

Exd/Exe Certified Brass Cable gland

M02354

Suitable for Steel Wire Armoured cables with outside diameter 15.5mm to 21.1mm (inner sheath 6.7mm to 14mm). Certified to ATEX (ll 2DG, Exd llC/Exe ll), IECEx, CSA, GOST-R and NEPSI standards. M20 x 1.5mm thread. Ingress protection to IP66/67/68.

Calibration adaptor

C03005

To enable calibration gas to be applied to the detector. One adaptor can be used for several detectors.

Downloads

Certificate

Datasheet

Manual